Technical data
Series
Logistics
Type
RMX-1223-E55
Applications
Measuring range
-25°C to +85°C
Accuracy
"±0,5°C (-20°C up to +85°C), ±1,0°C (-25°C up to -20°C)"
Resolution
0.1°C
WAN interface
SIM Card
Number of nodes supported
Memory
10082 samples
Buffer memory
Storage temperature
-40°C to +80°C
Sensors
2x wired external digital temperature sensors or external potential free contact intputs (non triggered)
Measuring rate
Standard 15 min, can be set 1 min to 24 h
Measuring mode
Online via IEEE802.15.4 wireless network (broadcast); Offline logging with periodic discover and dump (unicast)
Power
Battery operated 3.6V LiTCL AA type (included)
Battery life
Up to 2 years at measure interval 15min @ 25°C
Protection class
IP 67
Housing
ABS, HB-UL94
Dimensions
67 X 83 X 37mm
Weight
135g
Certifications
CE
Radio frequency
2.400-2.483,5 GHz (IEEE 802.15.4)
Transmit power
6.3mW (IEEE 802.15.4)
Transmission distance
Up to 60m indoor, 1000m outdoor (IEEE 802.15.4)
Energy consumption
Wireless
IEEE 802.15.4
Antenna
Internal wire or PCB antenna (IEEE 802.15.4)